A detailed ABSORBTION CHILLER DAILY preventive maintenance checklist

1. Visual Inspection

2. Fluid Levels

  • Locate the sight glass or level indicator.
  • Ensure the solution level is within the marked range.
  • If low, add the appropriate solution type.
  • Record any discrepancies in the maintenance log.
  • Access the refrigerant gauge ports.
  • Check the pressure readings against manufacturer specifications.
  • If levels are low, recharge with the correct refrigerant.
  • Document the findings in the maintenance log.
  • Locate the water level indicator or gauge.
  • Ensure the level is above the minimum threshold.
  • If low, add water to the system.
  • Record the water level in the maintenance log.
  • Locate the sight glass or level indicator.
  • Ensure the solution level is within the marked range.
  • If low, add the appropriate solution type.
  • Record any discrepancies in the maintenance log.
  • Access the refrigerant gauge ports.
  • Check the pressure readings against manufacturer specifications.
  • If levels are low, recharge with the correct refrigerant.
  • Document the findings in the maintenance log.
  • Locate the water level indicator or gauge.
  • Ensure the level is above the minimum threshold.
  • If low, add water to the system.
  • Record the water level in the maintenance log.
  • Check the level indicator on the chilled water tank.
  • Ensure it meets operational requirements.
  • If necessary, add chilled water.
  • Log the current levels for future reference.
  • Inspect the hot water level gauge on the generator.
  • Confirm it is within the optimal range.
  • If low, refill with hot water as needed.
  • Record the hot water levels in the maintenance log.
  • Identify and locate the fluid level indicators.
  • Check levels against recommended specifications.
  • Top off any fluids that are below the required level.
  • Document the status of all additional fluids.
  • Create or update a maintenance log entry.
  • Include date, time, and specific fluid levels checked.
  • Note any actions taken to adjust fluid levels.
  • Ensure log is accessible for future reviews.
  • Inspect all visible connections and seals for moisture.
  • Look for discoloration or residue indicating leaks.
  • Tighten any loose fittings or replace seals if necessary.
  • Report any leaks found in the maintenance log.
  • Review operational data and fluid level readings.
  • Make adjustments based on the current operating environment.
  • Add or remove fluids as needed to maintain optimal levels.
  • Record all adjustments in the maintenance log.
  • Test each fluid level sensor by manually checking levels.
  • Verify that alarms trigger at the appropriate levels.
  • Replace faulty sensors or alarms as needed.
  • Document the functionality status in the maintenance log.

3. Temperature and Pressure Readings

  • Use calibrated thermometers or temperature sensors.
  • Measure at consistent points for accuracy.
  • Log readings in a dedicated maintenance log.
  • Ensure temperatures are within operational guidelines.
  • Utilize appropriate pressure gauges.
  • Record readings for both absorber and generator.
  • Ensure gauges are calibrated and functioning.
  • Compare readings against standard operating pressures.
  • Check solution temperature using accurate sensors.
  • Log temperature readings regularly.
  • Verify against optimal temperature specifications.
  • Adjust system settings if temperatures are outside range.
  • Position thermometers at both inlet and outlet.
  • Ensure readings are taken simultaneously for comparison.
  • Log the differential temperature for efficiency review.
  • Check for consistency with previous readings.
  • Identify key measurement points in the system.
  • Use appropriate temperature sensors for accuracy.
  • Log all readings in the maintenance record.
  • Ensure refrigerant temperatures meet system specifications.
  • Calculate the temperature difference between inlet and outlet.
  • Ensure differential meets operational standards.
  • Document findings for performance assessment.
  • Investigate any significant variances from expected values.
  • Place a thermometer in a stable location in the chiller room.
  • Record ambient temperature regularly.
  • Assess how temperature affects system performance.
  • Ensure ventilation is adequate to maintain optimal conditions.
  • Perform calibration checks on all devices.
  • Replace or repair any malfunctioning sensors.
  • Document calibration status in maintenance records.
  • Schedule regular calibration intervals.
  • Measure pressure before and after each heat exchanger.
  • Calculate the pressure drop and log results.
  • Investigate significant pressure drops for potential issues.
  • Ensure maintenance is performed if fouling is detected.
  • Use pressure gauges to measure supply and return pressures.
  • Log all readings for reference.
  • Compare to operational standards for flow efficiency.
  • Investigate any discrepancies in expected pressure.
  • Create a dedicated log for anomalies.
  • Include date, time, and specific readings.
  • Assess trends over time for regular maintenance.
  • Report significant issues to maintenance supervisor.

4. Operational Checks

  • Inspect all indicator lights for proper illumination.
  • Check that all buttons and switches are responsive.
  • Ensure that digital displays show correct data.
  • Verify communication with the central monitoring system.
  • Manually operate each valve and actuator.
  • Listen for any unusual sounds during operation.
  • Check for leaks around valve seals.
  • Ensure that actuators return to their default position.
  • Note the time taken for each phase of the sequence.
  • Watch for error messages on control panels.
  • Listen for unusual noises during start-up and shutdown.
  • Check that all safety protocols are followed.
  • Compare current cooling output to specified targets.
  • Measure inlet and outlet temperatures.
  • Assess flow rates against design specifications.
  • Document any discrepancies and investigate causes.
  • Use vibration analysis tools to quantify levels.
  • Identify specific components producing noise.
  • Inspect mounting and support structures for looseness.
  • Record observations for future reference.
  • Check the solution flow rate against design specs.
  • Observe for any signs of foaming or contamination.
  • Verify temperature consistency throughout the system.
  • Ensure adequate levels of absorption solution.
  • Check for clean and clear burner surfaces.
  • Observe flame color and stability during operation.
  • Inspect for blockages in air or gas supply.
  • Ensure ignition sequences are functioning correctly.
  • Record inlet and outlet temperature readings.
  • Calculate temperature differential.
  • Compare with expected performance metrics.
  • Investigate any significant variances.
  • Use flow meters to obtain accurate readings.
  • Compare current measurements with manufacturer specifications.
  • Look for signs of refrigerant leakage.
  • Document any irregularities for follow-up.
  • Test each safety interlock manually.
  • Simulate alarm conditions to ensure activation.
  • Check indicator lights for operational status.
  • Review maintenance logs for past issues.
  • Access logs through the control panel interface.
  • Document any error codes and timestamps.
  • Cross-reference with troubleshooting guides.
  • Report unresolved issues to maintenance team.
  • Simulate an emergency situation safely.
  • Activate the shutdown procedure and observe response.
  • Ensure all systems cease operation promptly.
  • Document the time taken for complete shutdown.
  • Gather historical performance data for comparison.
  • Analyze current operation metrics against benchmarks.
  • Identify trends or deviations from expected performance.
  • Prepare a report summarizing findings.

5. Water Quality

  • Use calibrated pH meter and conductivity meter.
  • Collect water samples from designated points.
  • Record pH and conductivity readings.
  • Compare results with standard acceptable ranges.
  • Note any deviations for further analysis.
  • Check system indicators and alarms.
  • Verify flow rates and pressure gauges.
  • Look for leaks or unusual noises.
  • Ensure all valves are functioning correctly.
  • Document any irregularities or maintenance needs.
  • Visually inspect pipes and heat exchangers.
  • Look for discoloration, rust, or pitting.
  • Check for buildup of scale or deposits.
  • Use a corrosion meter if available.
  • Report and address any findings immediately.
  • Check system indicators and alarms.
  • Verify flow rates and pressure gauges.
  • Look for leaks or unusual noises.
  • Ensure all valves are functioning correctly.
  • Document any irregularities or maintenance needs.
  • Visually inspect pipes and heat exchangers.
  • Look for discoloration, rust, or pitting.
  • Check for buildup of scale or deposits.
  • Use a corrosion meter if available.
  • Report and address any findings immediately.
  • Use calibrated pH meter and conductivity meter.
  • Collect water samples from designated points.
  • Record pH and conductivity readings.
  • Compare results with standard acceptable ranges.
  • Note any deviations for further analysis.
  • Use a TDS meter to analyze water samples.
  • Collect samples from various system points.
  • Record TDS levels and refer to standards.
  • Identify sources if TDS exceeds acceptable limits.
  • Take corrective action as necessary.
  • Use a hardness test kit or titration method.
  • Collect water samples from the system.
  • Follow the kit instructions for accurate results.
  • Record hardness levels and compare to standards.
  • Initiate treatment if hardness is too high.
  • Inspect water tanks and piping visually.
  • Look for green or slimy residues.
  • Use a sample to check under a microscope if needed.
  • Note any findings and clean affected areas.
  • Consider chemical treatments if necessary.
  • Check pump operation and flow rates.
  • Inspect calibration settings and adjust if necessary.
  • Ensure chemical levels are adequate.
  • Document any pump maintenance performed.
  • Test dosing accuracy periodically.
  • Compile test results into a daily log.
  • Document any corrective actions performed.
  • Ensure records are clear and accessible.
  • Review findings with maintenance team.
  • Set follow-up actions if required.
  • Inspect filters for dirt and debris.
  • Clean or replace filters as necessary.
  • Check flow rates to ensure efficiency.
  • Document filter condition and maintenance.
  • Schedule regular filter inspections.
  • Check expiration dates on chemical containers.
  • Identify any chemicals that are low or empty.
  • Replace with fresh stock as needed.
  • Document any replacements made.
  • Ensure proper storage of chemicals.

6. Electrical Components

  • Examine all visible connections thoroughly.
  • Look for fraying, discoloration, or rust.
  • Ensure tightness of all connections.
  • Use a multimeter to check continuity.
  • Document any findings for repair.
  • Visually inspect fuses for any signs of damage.
  • Reset all circuit breakers and observe for tripping.
  • Test each fuse with a multimeter.
  • Replace any blown fuses immediately.
  • Log any replacements in maintenance records.
  • Measure voltage input at the control panel.
  • Compare readings with manufacturer specifications.
  • Inspect power supply connections for integrity.
  • Check for any signs of overheating.
  • Report discrepancies to maintenance supervisor.
  • Examine all visible connections thoroughly.
  • Look for fraying, discoloration, or rust.
  • Ensure tightness of all connections.
  • Use a multimeter to check continuity.
  • Document any findings for repair.
  • Visually inspect fuses for any signs of damage.
  • Reset all circuit breakers and observe for tripping.
  • Test each fuse with a multimeter.
  • Replace any blown fuses immediately.
  • Log any replacements in maintenance records.
  • Measure voltage input at the control panel.
  • Compare readings with manufacturer specifications.
  • Inspect power supply connections for integrity.
  • Check for any signs of overheating.
  • Report discrepancies to maintenance supervisor.
  • Inspect all wiring for signs of wear or exposure.
  • Ensure that wires are fastened and organized.
  • Check for any pinch points or sharp edges.
  • Use cable ties to secure loose wires.
  • Document any damaged wiring for replacement.
  • Activate each emergency shut-off switch.
  • Ensure the system responds appropriately.
  • Check for any unusual sounds or delays.
  • Reset the switch after testing.
  • Record the test results for future reference.
  • Listen for clicking sounds during operation.
  • Check for overheating or discoloration.
  • Ensure contacts are clean and free from debris.
  • Test operation using a multimeter.
  • Replace any malfunctioning components immediately.
  • Inspect all grounding connections visually.
  • Use a continuity tester to check effectiveness.
  • Ensure connections are tight and corrosion-free.
  • Refer to safety standards for compliance.
  • Document any issues for corrective action.
  • Power off the panel before cleaning.
  • Use a vacuum and soft brush for dust removal.
  • Inspect for any signs of moisture or corrosion.
  • Ensure all circuit labels are clear and readable.
  • Log cleaning activities in the maintenance log.
  • Identify key measurement points in the circuit.
  • Use a multimeter to take voltage readings.
  • Compare readings against manufacturer specifications.
  • Investigate any deviations from expected values.
  • Record measurements in maintenance documentation.
  • Test each indicator light and alarm system.
  • Observe for proper illumination and response.
  • Check for any persistent warning signals.
  • Replace faulty lights or alarms promptly.
  • Document tests and any necessary replacements.
  • Examine VFD displays for error codes.
  • Check settings against operational requirements.
  • Listen for unusual sounds during operation.
  • Test performance under different load conditions.
  • Record any findings for further review.
  • Access control system interface.
  • Verify settings against operating parameters.
  • Adjust any settings as necessary.
  • Document all changes made.
  • Schedule a follow-up review if needed.
  • Create a detailed report of findings.
  • Include specific locations and descriptions of issues.
  • Prioritize issues based on severity.
  • Distribute report to relevant maintenance personnel.
  • Schedule follow-up actions as necessary.

7. Documentation and Reporting

8. Safety Checks

  • Inspect all guards and covers for damage or displacement.
  • Ensure all fasteners are tightened and secure.
  • Replace any missing or broken guards immediately.
  • Test the emergency shut-off switch to ensure it operates correctly.
  • Inspect wiring and connections for damage.
  • Document any issues and perform repairs as needed.
  • Distribute updated safety protocol documents to all staff.
  • Conduct a brief meeting to review emergency procedures.
  • Ensure all personnel can articulate the emergency procedures.
  • Inspect all guards and covers for damage or displacement.
  • Ensure all fasteners are tightened and secure.
  • Replace any missing or broken guards immediately.
  • Test the emergency shut-off switch to ensure it operates correctly.
  • Inspect wiring and connections for damage.
  • Document any issues and perform repairs as needed.
  • Distribute updated safety protocol documents to all staff.
  • Conduct a brief meeting to review emergency procedures.
  • Ensure all personnel can articulate the emergency procedures.
  • Check the pressure gauge on each extinguisher.
  • Verify that extinguishers are mounted in designated locations.
  • Ensure inspection tags are current and visible.
  • Inspect all labels for wear or fading.
  • Replace any illegible or missing labels immediately.
  • Ensure signs are positioned where they are easily seen.
  • Inspect ventilation ducts for blockages or obstructions.
  • Ensure exhaust fans operate correctly.
  • Monitor temperature and air quality indicators.
  • Activate alarms to confirm they sound and illuminate.
  • Check for any faults or error messages in alarm systems.
  • Document and address any malfunctioning alarms.
  • Inspect PPE for signs of wear or damage.
  • Ensure an adequate supply of PPE is available for all personnel.
  • Replace any damaged or expired equipment immediately.
  • Look for discoloration or melted components.
  • Check that all panel doors are closed and secured.
  • Document any irregularities and schedule repairs if necessary.
  • Check expiration dates on all supplies.
  • Restock any used or expired items.
  • Ensure the kit is easily accessible to all personnel.
  • Inspect all walkways and emergency exits for items blocking access.
  • Remove any debris or equipment obstructing pathways.
  • Mark pathways clearly if needed.
  • Identify potential hazards in the chiller area.
  • Evaluate risks and determine mitigation strategies.
  • Document findings and communicate them to staff.
  • Verify training records for each employee.
  • Conduct refresher training sessions as required.
  • Encourage adherence to safety practices through regular reminders.

Related Checklists