A detailed Air Cooled Compression Chiller WEEKLY preventive maintenance checklist

General Inspection

  • Examine external casing for dents, rust, or cracks.
  • Check for any loose components or fasteners.
  • Look for evidence of oil or refrigerant leaks.
  • Inspect electrical connections for corrosion or fraying.
  • Listen for grinding, squealing, or rattling sounds.
  • Identify if noises vary with changes in load or speed.
  • Use a stethoscope for detailed sound localization.
  • Document any persistent sounds for further analysis.
  • Inspect all joints and fittings for signs of leaks.
  • Use a leak detection solution to identify gas leaks.
  • Check around the compressor and evaporator connections.
  • Monitor for any moisture accumulation around the unit.
  • Inspect hinges and latches for proper function.
  • Ensure no gaps exist when panels are closed.
  • Check for any signs of tampering or damage.
  • Confirm that safety interlocks are operational.
  • Look for tears, cracks, or signs of moisture intrusion.
  • Ensure insulation is securely fastened along the lines.
  • Assess for any signs of mold or mildew growth.
  • Replace any damaged insulation immediately.
  • Examine all mounting bolts and brackets for rust.
  • Check for any signs of movement or shifting.
  • Ensure supports are stable and securely anchored.
  • Document any structural concerns for repair.
  • Check for droppings, nests, or chew marks.
  • Inspect insulation and hidden areas for pests.
  • Seal any entry points to prevent future infestations.
  • Consult pest control if infestation is confirmed.
  • Clear any plants, leaves, or trash near the unit.
  • Maintain at least three feet of clearance around the chiller.
  • Inspect for any potential fire hazards nearby.
  • Ensure proper drainage to prevent water pooling.
  • Inspect all labels for fading, peeling, or damage.
  • Ensure that safety and operational labels are visible.
  • Replace any illegible labels with new ones.
  • Verify that all tags reflect current information.
  • Look for cracks, tears, or excessive wear on pads.
  • Ensure mounts are securely fastened and not degraded.
  • Check for any signs of rust or corrosion.
  • Replace worn pads to reduce vibration transmission.
  • Ensure drain pan is free of obstructions.
  • Check for standing water or overflow conditions.
  • Look for algae or mold and clean as needed.
  • Verify that the drain lines are clear and functional.
  • Use a level to check across the top of the chiller.
  • Adjust feet or use shims as necessary for leveling.
  • Ensure that the unit is not leaning or tilted.
  • Document adjustments made for future reference.
  • Wipe down surfaces to remove dust and grime.
  • Check fans and coils for dust buildup.
  • Ensure no debris is stuck in the unit's airflow areas.
  • Maintain a regular cleaning schedule to prevent buildup.

Electrical Components

  • Use a torque wrench to check tightness.
  • Look for any discoloration or rust.
  • Clean connections with a suitable electrical contact cleaner.
  • Check all indicator lights for functionality.
  • Test buttons and switches for responsiveness.
  • Ensure display screens show correct readings.
  • Press each emergency stop button firmly.
  • Verify that all equipment stops immediately.
  • Reset the system to ensure normal operation.
  • Inspect fuses for visible damage or burns.
  • Test circuit breakers by toggling on and off.
  • Replace any faulty components immediately.
  • Look for fraying, discoloration, or exposed wiring.
  • Check for signs of overheating like melting.
  • Ensure all connections are secure and intact.
  • Inspect grounding connections for corrosion.
  • Verify tightness using a torque wrench.
  • Test grounding continuity with a multimeter.
  • Listen for clicking sounds during operation.
  • Check for overheating or discoloration.
  • Test operation using a multimeter.
  • Use a multimeter to check voltage levels.
  • Measure current with a clamp meter.
  • Compare readings to manufacturer specifications.
  • Power down the system before cleaning.
  • Use a dry cloth to wipe surfaces.
  • Avoid using liquid cleaners on electrical components.
  • Listen for grinding, humming, or rattling sounds.
  • Inspect components for loose parts.
  • Document any abnormalities for further investigation.
  • Compare current system with existing diagrams.
  • Update any changes in wiring or components.
  • File the revised schematics in a designated location.
  • Run a test cycle on the timers or PLCs.
  • Check for correct timing and sequence.
  • Document any discrepancies for troubleshooting.
  • Inspect all labels for visibility and clarity.
  • Replace faded labels with new, clear ones.
  • Use a labeling machine for consistency.

Refrigerant System

  • Use a gauge to measure refrigerant levels.
  • Inspect joints and fittings for signs of leakage.
  • Apply soapy water on suspected areas to check for bubbles.
  • Document any leaks found and plan for repair.
  • Take readings from pressure gauges and temperature probes.
  • Compare values against manufacturer specifications.
  • Record readings for future reference.
  • Investigate any deviations from normal parameters.
  • Check the sight glass for clear visibility.
  • Look for bubbles, indicating low refrigerant levels.
  • Ensure the sight glass is free from contaminants.
  • Document findings and address any issues.
  • Examine lines for any physical damage or corrosion.
  • Check for signs of rust, cracks, or pinholes.
  • Ensure all lines are securely fastened.
  • Report any damaged lines for replacement.
  • Locate all service ports on the refrigerant system.
  • Check for physical damage or blockage.
  • Ensure caps are present and in good condition.
  • Document any accessibility issues.
  • Check for proper operation of the expansion valve.
  • Listen for unusual sounds during operation.
  • Adjust settings according to manufacturer guidelines.
  • Document any adjustments made.
  • Inspect the receiver for any debris or contaminants.
  • Check for proper refrigerant flow into the receiver.
  • Ensure that the receiver is not overfilled.
  • Document the condition and any necessary cleaning.
  • Check insulation for tears, wear, or moisture.
  • Ensure insulation is properly fitted and secured.
  • Replace damaged insulation as needed.
  • Document insulation condition and any replacements.
  • Tighten any loose connections using appropriate tools.
  • Inspect connections for signs of leakage.
  • Use leak detection methods to verify integrity.
  • Document the condition of connections.
  • Listen for abnormal sounds during operation.
  • Check for excessive vibrations during compressor operation.
  • Inspect mounting and support structures for stability.
  • Document any concerns for further investigation.
  • Log ambient temperature and humidity levels.
  • Record operating temperatures and pressures.
  • Compare recorded data against historical performance.
  • Identify any trends that may require attention.
  • Verify the type of refrigerant in use.
  • Consult the manufacturer’s specifications for the correct refrigerant.
  • Check labels on refrigerant containers for compliance.
  • Document any discrepancies found.
  • Check current refrigerant inventory against records.
  • Update records to reflect any changes made.
  • Ensure compliance with local regulations on refrigerant management.
  • Document completed inventory reviews.
  • Identify refrigerants needing recovery or disposal.
  • Schedule appointments with certified technicians.
  • Document all recovery and disposal actions taken.
  • Ensure compliance with environmental regulations.
  • Check accumulator for signs of liquid refrigerant presence.
  • Inspect for blockages or restrictions in flow.
  • Ensure proper insulation and mounting of the accumulator.
  • Document findings and any issues.
  • Inspect refrigerant lines for frost or ice buildup.
  • Determine if frost indicates low refrigerant levels.
  • Check insulation and airflow around affected areas.
  • Document any frost issues and recommend actions.
  • Activate the electronic expansion valve and monitor performance.
  • Check for proper opening and closing response.
  • Verify control signals are functioning correctly.
  • Document any operational issues found.

Cooling Fans

  • Listen for unusual sounds during operation.
  • Check for smooth fan rotation without any wobbling.
  • Ensure fans start and stop correctly without delays.
  • Monitor the power consumption to identify irregularities.
  • Turn off and isolate power to the fans.
  • Use a soft brush or vacuum to remove loose debris.
  • Wipe blades with a damp cloth to eliminate stubborn dirt.
  • Ensure surrounding areas are free of obstructions.
  • Identify lubrication points on the motor.
  • Use appropriate lubricant as per manufacturer specifications.
  • Apply lubricant without over-saturating or spilling.
  • Check for any signs of leakage post-lubrication.
  • Inspect for cracks, chips, or deformities on blades.
  • Ensure blades are securely attached to the hub.
  • Compare with replacement blades to confirm compatibility.
  • Document any replacements made for record-keeping.
  • Inspect belts for wear, fraying, or cracking.
  • Use a tension gauge to check proper tension.
  • Adjust tension as required according to specifications.
  • Replace belts that are damaged or worn.
  • Check for rust, dents, or cracks in the housing.
  • Clean any rusted areas and apply protective coating.
  • Ensure all screws and fasteners are intact.
  • Replace damaged housing if structural integrity is compromised.
  • Check bolts and screws for tightness.
  • Inspect mounts for any signs of wear or damage.
  • Use a vibration meter to check for excessive vibration.
  • Repair or replace any faulty mounts as necessary.
  • Use a tachometer to measure fan speed.
  • Compare measured speed to manufacturer’s specifications.
  • Adjust speed settings if necessary to match specs.
  • Document any discrepancies for follow-up.
  • Inspect wiring for signs of wear, melting, or discoloration.
  • Ensure all connections are tight and secure.
  • Use a multimeter to check for continuity.
  • Replace any damaged wires or connectors.
  • Measure airflow at the outlet of the fan.
  • Compare readings to manufacturer specifications.
  • Identify any restrictions or blockages affecting airflow.
  • Make necessary adjustments to improve airflow.
  • Check control panel settings for accuracy.
  • Test manual overrides if applicable.
  • Ensure automatic settings respond correctly.
  • Document any anomalies in control operation.
  • Record date and time of inspection.
  • List any issues found and corrective actions taken.
  • Note any parts replaced or serviced.
  • Ensure documentation is filed in maintenance records.

Filters and Airflow

  • Turn off the chiller and ensure safety protocols are followed.
  • Remove the air filter from its compartment.
  • Inspect for dirt, dust, or blockages.
  • Replace with a new filter if heavily soiled.
  • Reinstall the filter securely and restore power.
  • Visual check for any debris or objects near intake/discharge.
  • Remove any obstructions like leaves, trash, or equipment.
  • Ensure there are no structural barriers.
  • Document any findings and actions taken.
  • Check a clearance zone of at least 3 feet around the unit.
  • Remove any nearby equipment or materials.
  • Ensure no outdoor plants or structures block airflow.
  • Confirm that airflow is not restricted by nearby fences.
  • Turn off the chiller and disconnect power.
  • Remove the air filters from their housing.
  • Use mild soap and water to wash filters thoroughly.
  • Rinse and allow filters to dry completely before reinstallation.
  • Reinstall filters securely and restore power.
  • Visually examine ductwork for visible damage or corrosion.
  • Check for gaps or cracks in joints and seams.
  • Use a smoke pencil to identify air leaks.
  • Seal any identified leaks with appropriate duct tape or sealant.
  • Ensure ducts are properly insulated.
  • Locate the airflow measurement points as specified by the manufacturer.
  • Turn on the chiller and allow it to stabilize.
  • Use an anemometer to measure airflow at each point.
  • Compare readings to manufacturer specifications.
  • Document any discrepancies for further investigation.
  • Inspect all duct connections for secure fittings.
  • Ensure ducts are straight and free from bends.
  • Adjust or realign ducts as necessary.
  • Tighten any loose connections with appropriate fasteners.
  • Confirm that no obstructions are present.
  • Turn off power to the chiller before inspection.
  • Remove any protective covers from fans.
  • Inspect blades for dirt, debris, or physical damage.
  • Clean blades using a soft brush or cloth.
  • Replace any damaged blades as needed.
  • Check the manufacturer's specifications for fan speed.
  • Use a tachometer to measure fan RPM.
  • Compare RPM readings with specifications.
  • Adjust fan speed settings if necessary.
  • Ensure all electrical connections are secure.
  • Inspect intake areas for visible mold or mildew.
  • Use a cleaning solution to remove any growth.
  • Ensure proper drainage to prevent future growth.
  • Improve ventilation if necessary to reduce humidity.
  • Consider using anti-microbial treatments if needed.
  • Inspect access panels for secure closure.
  • Check for missing or damaged latches and seals.
  • Repair or replace any faulty components.
  • Ensure all panels are properly aligned and fit snugly.
  • Document any issues and schedule repairs as needed.
  • Check the temperature and humidity around the unit.
  • Ensure there are no obstructions within the airflow path.
  • Monitor environmental changes that may affect performance.
  • Adjust landscaping or structures if necessary.
  • Record conditions for future reference.
  • Create a cleaning schedule based on environmental conditions.
  • Use a soft brush or cloth to remove dust and debris.
  • Clean the condenser coils carefully to maintain efficiency.
  • Inspect for signs of corrosion or wear during cleaning.
  • Document cleaning activities for maintenance records.

Condenser Coils

  • Look for dirt, dust, and debris on the surface.
  • Check for physical damage like dents or cracks.
  • Note any areas of discoloration or wear.
  • Use a soft brush to gently remove dirt.
  • Apply a manufacturer-approved cleaning solution.
  • Rinse thoroughly with water to remove residue.
  • Inspect for rust or flaking paint.
  • Look for white chalky deposits indicating scaling.
  • Document any areas requiring treatment or repair.
  • Examine fins for bends or kinks.
  • Use a fin comb to straighten any bent fins.
  • Ensure fins are evenly spaced and not obstructing airflow.
  • Inspect the area surrounding the coils.
  • Remove any leaves, trash, or equipment nearby.
  • Confirm that vents are clear for optimal airflow.
  • Check all mounting brackets and supports.
  • Ensure there is no rust or wear on supports.
  • Tighten any loose connections as necessary.
  • Inspect joints and connections for oil residue.
  • Use a leak detection solution if needed.
  • Report and repair any detected leaks immediately.
  • Measure the inlet air temperature.
  • Measure the outlet air temperature.
  • Calculate the differential and compare with specifications.
  • Inspect insulation for tears, wear, or moisture.
  • Replace any damaged or missing insulation.
  • Ensure insulation is securely fitted to prevent energy loss.
  • Check the drain pan for clogs or debris.
  • Ensure water flows freely through the drain.
  • Look for signs of rust or water damage.
  • Listen for unusual noises from the fan motor.
  • Check the fan speed and functionality.
  • Ensure that the fan is effectively cooling the coils.
  • Record findings in the maintenance log.
  • Note any corrective actions taken.
  • Schedule follow-up tasks for unresolved issues.

Drainage System

  • Visually examine the drain for any visible clogs.
  • Use a flashlight to check hard-to-see areas.
  • Clear any blockages using a flexible brush or compressed air if necessary.
  • Remove any leaves, dust, or other debris from the drain pan.
  • Wipe down the pan with a damp cloth.
  • Inspect for rust or damage and address any issues.
  • Listen for operational sounds from the pump.
  • Check the pump's electrical connections for any loose wires.
  • Observe the pump while it operates to ensure it is effectively removing water.
  • Look for water stains or pooling near connections.
  • Check for corrosion or wear on the joints.
  • Tighten any loose fittings to prevent leaks.
  • Use a level to check the slope of the drain line.
  • Ensure the slope is directed toward the drainage point.
  • Adjust the line if necessary to maintain proper drainage.
  • Manually lift the float switch to observe the pump operation.
  • Ensure the pump activates as the float is raised.
  • Reset the float switch and check for proper return operation.
  • Inspect the surface of the drain pan for discoloration.
  • Use a suitable cleaner to scrub away any growth.
  • Rinse the pan thoroughly after cleaning.
  • Check the insulation for tears, holes, or moisture damage.
  • Replace any damaged insulation as needed.
  • Ensure insulation is securely attached to the drain lines.
  • Check all connections for tightness.
  • Look for any signs of wear that could cause disconnection.
  • Reinforce connections if necessary to ensure security.
  • Walk around the chiller unit to inspect for any signs of water accumulation.
  • Check the ground and surfaces for dampness.
  • Document any findings for further investigation.
  • Use a dedicated section in the maintenance log for drainage notes.
  • Include details on any issues found and actions taken.
  • Sign and date the log entry for accountability.

Safety Devices

  • Ensure valves are accessible.
  • Open and close valves manually.
  • Check for leaks or unusual noises.
  • Confirm that valves return to closed position.
  • Document any issues for repair.
  • Locate cutouts on the chiller.
  • Manually trigger cutouts to verify operation.
  • Check reset mechanisms for proper function.
  • Ensure indicator lights are operational.
  • Replace any faulty components immediately.
  • Test alarm activation by simulating faults.
  • Listen for audible alarms and check visual indicators.
  • Ensure alarms reset correctly after testing.
  • Check alarm documentation for any discrepancies.
  • Report any non-functional alarms for maintenance.
  • Identify thermal protection devices in the system.
  • Test devices by exceeding temperature limits safely.
  • Confirm devices activate and shut down equipment.
  • Inspect for any physical damage or wear.
  • Document and address any failures immediately.
  • Locate all interlocks and switches.
  • Test each switch for proper functionality.
  • Check for signs of wear or damage.
  • Ensure that switches are easily accessible.
  • Document any issues and schedule repairs.
  • Use a certified pressure gauge for comparison.
  • Check readings against known pressure values.
  • Calibrate or replace gauges that are inaccurate.
  • Ensure mounting is secure and stable.
  • Document calibration results for maintenance records.
  • Activate alarms to test sound and visibility.
  • Ensure alarms are loud enough and lights are bright.
  • Check reset functions for proper operation.
  • Inspect connections for wear or corrosion.
  • Document any alarms that fail to operate.
  • Conduct a visual inspection of all wiring.
  • Look for frayed wires, loose connections, or corrosion.
  • Check insulation for integrity.
  • Ensure all connections are tight and secure.
  • Report any damaged wiring for immediate repair.
  • Inspect pathways and access points to safety devices.
  • Remove any obstructions or hazards.
  • Mark emergency access points clearly.
  • Ensure access is known to all personnel.
  • Document any access issues found.
  • Check existing documentation for relevance.
  • Update labels to reflect current device status.
  • Ensure all safety devices are clearly labeled.
  • Archive outdated documents appropriately.
  • Distribute updated documentation to relevant staff.
  • Inspect all safety devices and associated hardware.
  • Look for rust, corrosion, or physical cracks.
  • Check for any loose components or fittings.
  • Document findings and schedule repairs as needed.
  • Ensure inspection is thorough and systematic.

Documentation

Related Checklists