A detailed Water Cooled Compression Chiller ANNUAL preventive maintenance checklist

1. Safety Precautions

  • Select appropriate gloves and goggles based on the materials handled.
  • Inspect safety gear for any damage or wear before use.
  • Ensure gear fits properly to provide maximum protection.
  • Wear additional protective clothing if necessary.
  • Locate the main power disconnect switch.
  • Ensure the switch is in the OFF position before proceeding.
  • Verify that the power indicator light is off.
  • Place a warning sign near the power source.
  • Identify all energy sources connected to the chiller.
  • Apply lockout devices to all energy isolating devices.
  • Attach a tagout label with date and names of authorized personnel.
  • Verify isolation by attempting to operate the chiller controls.
  • Locate the SDS for each refrigerant used in the chiller.
  • Review hazards, handling, and emergency procedures listed.
  • Ensure all personnel understand the information provided.
  • Keep a copy of the SDS accessible in the work area.
  • Open windows and doors to promote air circulation.
  • Use exhaust fans to enhance ventilation if necessary.
  • Monitor air quality with appropriate detection equipment.
  • Ensure that ventilation systems are operational.
  • Inspect refrigerant lines visually for signs of oil or frost.
  • Use leak detection equipment to identify potential leaks.
  • Document any findings and report them immediately.
  • Do not proceed with maintenance if leaks are detected.
  • Assess the weight of components before lifting.
  • Use mechanical aids like dollies or hoists as needed.
  • Employ proper body mechanics: lift with legs, not back.
  • Seek assistance if the load is too heavy.
  • Check the first aid kit for completeness and expiration dates.
  • Ensure all personnel know the kit's location.
  • Restock supplies as needed to maintain readiness.
  • Familiarize with the contents of the kit.
  • Ensure the fire extinguisher is easily reachable.
  • Check that the extinguisher is fully charged and not expired.
  • Inspect the extinguisher for any physical damage.
  • Review the operating instructions on the extinguisher.
  • Gather all personnel involved in the maintenance.
  • Discuss potential hazards and safety measures to be taken.
  • Assign roles and responsibilities for the maintenance task.
  • Encourage questions and clarify any uncertainties.
  • Review emergency procedures for refrigerant leaks or exposure.
  • Ensure everyone knows how to use protective equipment.
  • Conduct refreshers on emergency response protocols.
  • Confirm that all personnel have completed required training.
  • Inspect tools for wear and functionality before use.
  • Use only tools designed for the specific maintenance tasks.
  • Replace or repair any damaged tools immediately.
  • Keep tools organized and within easy reach.
  • Remove any unnecessary tools or materials from the area.
  • Organize equipment and materials logically and safely.
  • Maintain clear pathways for movement and emergency exits.
  • Conduct regular checks during maintenance to minimize clutter.
  • Verify that all associated equipment is powered down.
  • Use lockout/tagout procedures to ensure isolation.
  • Communicate with all personnel about the isolation status.
  • Document the isolation procedures followed.

2. Visual Inspection

  • Inspect joints, fittings, and seals.
  • Look for water spots or corrosion.
  • Use a flashlight for better visibility.
  • Check both the refrigerant and water circuits.
  • Look for rust, paint peeling, or dents.
  • Check for any sharp edges or protrusions.
  • Ensure that the housing is secure and intact.
  • Check for any tears or gaps in insulation.
  • Look for condensation or moisture on pipes.
  • Ensure that insulation is properly secured.
  • Check terminals for corrosion or loose connections.
  • Look for frayed wires or damaged insulation.
  • Ensure connections are clean and securely fastened.
  • Inspect joints, fittings, and seals.
  • Look for water spots or corrosion.
  • Use a flashlight for better visibility.
  • Check both the refrigerant and water circuits.
  • Look for rust, paint peeling, or dents.
  • Check for any sharp edges or protrusions.
  • Ensure that the housing is secure and intact.
  • Check for any tears or gaps in insulation.
  • Look for condensation or moisture on pipes.
  • Ensure that insulation is properly secured.
  • Check terminals for corrosion or loose connections.
  • Look for frayed wires or damaged insulation.
  • Ensure connections are clean and securely fastened.
  • Listen for unusual noises during operation.
  • Check alignment of rotating components.
  • Inspect mounts and supports for wear.
  • Check coils for dirt buildup or blockages.
  • Use a soft brush or vacuum for cleaning.
  • Ensure airflow is unobstructed around coils.
  • Check strainers for accumulated debris.
  • Look for signs of scaling or corrosion.
  • Ensure water flow is unobstructed.
  • Inspect blades for damage or wear.
  • Ensure blades are securely attached.
  • Check for proper rotation direction.
  • Inspect isolators for cracks or deterioration.
  • Check mounting pads for signs of wear.
  • Ensure pads are securely fastened.
  • Look for standing water in drain pans.
  • Check for algae or mold buildup.
  • Ensure lines are clear and draining properly.
  • Check for discoloration or burnt smells.
  • Ensure motors are free of dust and debris.
  • Inspect cooling fans for proper operation.
  • Look for droppings or nesting materials.
  • Inspect for entry points around the unit.
  • Consider pest control measures if needed.
  • Check all screws and fasteners for tightness.
  • Look for damage or misalignment on panels.
  • Ensure gaskets are intact to prevent leaks.
  • Inspect guards for cracks or missing sections.
  • Ensure covers are securely attached.
  • Replace any damaged safety features immediately.
  • Check for leaks around tanks and fittings.
  • Inspect filters for clogs or deterioration.
  • Ensure system components are functioning properly.

3. Water System Maintenance

  • Inspect all joints, fittings, and connections.
  • Look for moisture or water stains around pipes.
  • Use a leak detection solution if necessary.
  • Document any identified leaks for repair.
  • Remove strainer and filters from the water system.
  • Rinse with clean water to remove debris.
  • Inspect for any physical damage or wear.
  • Reinstall components securely after cleaning.
  • Use appropriate test kits to measure chemicals.
  • Adjust levels according to manufacturer's specifications.
  • Add chemicals slowly to avoid shock to the system.
  • Record chemical levels and adjustments made.
  • Check fan operation and water distribution.
  • Remove debris from the cooling tower basin.
  • Inspect fill media for blockages or scaling.
  • Document any cleaning or repairs needed.
  • Inspect all joints, fittings, and connections.
  • Look for moisture or water stains around pipes.
  • Use a leak detection solution if necessary.
  • Document any identified leaks for repair.
  • Remove strainer and filters from the water system.
  • Rinse with clean water to remove debris.
  • Inspect for any physical damage or wear.
  • Reinstall components securely after cleaning.
  • Use appropriate test kits to measure chemicals.
  • Adjust levels according to manufacturer's specifications.
  • Add chemicals slowly to avoid shock to the system.
  • Record chemical levels and adjustments made.
  • Check fan operation and water distribution.
  • Remove debris from the cooling tower basin.
  • Inspect fill media for blockages or scaling.
  • Document any cleaning or repairs needed.
  • Check for unusual noises or vibrations during operation.
  • Inspect seals and bearings for wear.
  • Clean any obstructions from the pump intake.
  • Verify that flow rates meet specifications.
  • Use flow meters to measure water flow rate.
  • Compare readings to system design specifications.
  • Adjust valves to increase or decrease flow as needed.
  • Document flow adjustments for future reference.
  • Check the pressure gauge for correct readings.
  • Ensure water level is within the recommended range.
  • Inspect for signs of leaks or corrosion.
  • Adjust pressure as needed and document findings.
  • Operate each valve to ensure proper functionality.
  • Check for leaks around valve bodies and seals.
  • Lubricate moving parts if necessary.
  • Document any repairs or replacements needed.
  • Inspect visible piping and components for discoloration.
  • Use a wire brush to remove scale buildup.
  • Treat any corroded areas with appropriate products.
  • Document findings and any corrective actions taken.
  • Check for tears, moisture, or mold on insulation.
  • Replace any damaged insulation to maintain efficiency.
  • Ensure insulation is securely fitted to pipes.
  • Document any repairs or replacements performed.
  • Manually test float switches to ensure they operate.
  • Check for proper response of level controls.
  • Inspect wiring and connections for integrity.
  • Document any issues found during testing.
  • Check venting pipes for blockages or restrictions.
  • Ensure vents are positioned correctly in the system.
  • Bleed air from the system if necessary.
  • Document venting checks and any adjustments made.
  • Look for discoloration or slimy residue in tanks.
  • Check for odors that indicate biological growth.
  • Use appropriate biocides if growth is detected.
  • Document findings and any treatment applied.
  • Evaluate current system performance against seasonal expectations.
  • Adjust water treatment and flow rates as needed.
  • Ensure system settings are optimized for seasonal demand.
  • Document any adjustments made for future reference.
  • Keep a detailed log of all findings and actions taken.
  • Include dates, personnel involved, and materials used.
  • Store documentation in a central maintenance record.
  • Review logs periodically for recurring issues.

4. Compressor Maintenance

  • Remove the oil level sight glass or dipstick.
  • Inspect oil color and clarity for signs of contamination.
  • Check oil level against manufacturer specifications.
  • Add oil if necessary, using the recommended type.
  • Locate the oil filter as per the manufacturer’s guidelines.
  • Prepare a suitable container to catch any spilled oil.
  • Remove the old filter and check for debris.
  • Install a new filter ensuring proper tightness.
  • Power on the compressor and listen for abnormal sounds.
  • Check for vibrations by placing your hand on the unit.
  • Look for any signs of wear or misalignment.
  • Document any unusual findings for further investigation.
  • Use a calibrated gauge to check the pressure settings.
  • Adjust the controls according to manufacturer specifications.
  • Test the system to ensure it operates within normal parameters.
  • Record the calibration results in the maintenance log.
  • Remove the air intake filter following safety protocols.
  • Inspect for dirt, debris, and signs of damage.
  • Clean the filter with compressed air or replace if necessary.
  • Reinstall the filter securely after cleaning.
  • Use a leak detection solution to check for bubbles.
  • Inspect all joints and connections for signs of leaks.
  • Repair any identified leaks as per safety regulations.
  • Document all findings and repairs made.
  • Test the start button to ensure the compressor powers on.
  • Observe the compressor during startup for smooth operation.
  • Check the stop control by powering off the unit.
  • Confirm that controls are responsive and functioning correctly.
  • Turn off the compressor and allow it to cool.
  • Use a soft brush or vacuum to remove dust and debris.
  • Inspect for any signs of damage or corrosion.
  • Ensure coils are free from obstructions for efficient operation.
  • Use a dial indicator to measure shaft alignment.
  • Adjust alignment as necessary to meet manufacturer specifications.
  • Ensure all mounting bolts are secure after adjustments.
  • Document alignment results in the maintenance record.
  • Connect an ammeter to the compressor’s power supply.
  • Record the running amperage during normal operation.
  • Compare readings to the specifications provided by the manufacturer.
  • Investigate any significant discrepancies found.
  • Power down the compressor before inspection.
  • Use a wrench to check the tightness of each connection.
  • Look for signs of corrosion or wear on terminals.
  • Tighten any loose connections and document the process.
  • Access the maintenance logs and operational data.
  • Identify any patterns or frequent issues reported.
  • Analyze the data for potential root causes.
  • Develop a plan to address any recurring problems.
  • Inspect safety devices visually for any signs of wear.
  • Test the pressure relief valve according to safety protocols.
  • Ensure devices reset properly after testing.
  • Document the condition and functionality of all safety devices.
  • Refer to the maintenance manual for lubrication points.
  • Use the correct type of lubricant as specified.
  • Apply lubricant evenly and avoid over-lubrication.
  • Check for excess lubricant and clean if necessary.
  • Use a maintenance log or digital system for documentation.
  • Include date, time, and details of all actions taken.
  • Note any parts replaced or issues identified.
  • Ensure records are accessible for future reference.

5. Refrigerant System Checks

  • Use a refrigerant gauge to check levels.
  • Compare readings with manufacturer's specifications.
  • Recharge with the appropriate refrigerant type if levels are low.
  • Document the amount of refrigerant added.
  • Check insulation for any wear or damage.
  • Look for visible signs of refrigerant leaks.
  • Use leak detection solutions on joints and fittings.
  • Replace damaged insulation if necessary.
  • Verify pressure switch settings against specifications.
  • Calibrate sensors using appropriate testing equipment.
  • Check for proper operation at various load conditions.
  • Document any adjustments made during testing.
  • Check for proper valve positioning during operation.
  • Ensure there are no unusual noises indicating malfunction.
  • Test temperature differences across the valve.
  • Replace if the valve is not functioning correctly.
  • Use a refrigerant gauge to check levels.
  • Compare readings with manufacturer's specifications.
  • Recharge with the appropriate refrigerant type if levels are low.
  • Document the amount of refrigerant added.
  • Check insulation for any wear or damage.
  • Look for visible signs of refrigerant leaks.
  • Use leak detection solutions on joints and fittings.
  • Replace damaged insulation if necessary.
  • Verify pressure switch settings against specifications.
  • Calibrate sensors using appropriate testing equipment.
  • Check for proper operation at various load conditions.
  • Document any adjustments made during testing.
  • Check for proper valve positioning during operation.
  • Ensure there are no unusual noises indicating malfunction.
  • Test temperature differences across the valve.
  • Replace if the valve is not functioning correctly.

6. Electrical System Inspection

  • Use a torque wrench to check connections.
  • Ensure all terminals are securely fastened.
  • Look for signs of oxidation or corrosion.
  • Document any loose connections for follow-up.
  • Identify and remove any blown fuses.
  • Inspect circuit breakers for tripping issues.
  • Replace fuses with the correct amperage rating.
  • Test the system after replacements to ensure functionality.
  • Inspect all indicator lights for proper function.
  • Verify that control buttons respond correctly.
  • Check for error messages or alarms.
  • Document any irregularities for troubleshooting.
  • Power down the system before inspection.
  • Remove dust and debris from contactors.
  • Check for pitting or wear on contact points.
  • Test operation after cleaning to ensure effectiveness.
  • Check grounding connections for integrity.
  • Use a multimeter to test ground resistance.
  • Ensure grounding wires are securely connected.
  • Document grounding status for compliance records.
  • Use a multimeter to measure voltage levels.
  • Check current draw at designated points.
  • Compare readings against manufacturer specifications.
  • Report any discrepancies for further investigation.
  • Examine insulation for cracks or fraying.
  • Look for discoloration indicating overheating.
  • Check for corrosion on terminals and connectors.
  • Replace damaged wiring as necessary.
  • Inspect for burnt components or discoloration.
  • Ensure no loose connections on the boards.
  • Test functionality of each circuit board.
  • Document any issues for repairs.
  • Simulate emergency conditions to test switches.
  • Ensure switches activate and deactivate correctly.
  • Inspect interlocks for proper engagement.
  • Document test results and any needed repairs.
  • Check for discoloration or warping of the casing.
  • Look for any oil stains or puddles.
  • Verify temperature readings against specifications.
  • Report any abnormalities for immediate attention.
  • Inspect seals and gaskets for wear.
  • Check enclosures for dust or moisture ingress.
  • Clean any contaminants inside enclosures.
  • Replace damaged seals to maintain integrity.
  • Access maintenance logs for past repairs.
  • Identify patterns or frequent problems.
  • Discuss findings with maintenance team.
  • Plan preventive measures based on historical data.
  • Check for fading or peeling labels.
  • Ensure all markings are compliant with regulations.
  • Replace any illegible labels promptly.
  • Document any changes made for records.
  • Initiate alarm tests to verify functionality.
  • Check response time of indicators.
  • Inspect wiring connected to alarm systems.
  • Document test results and any required repairs.

7. Performance Testing

  • Use calibrated thermometers for accurate readings.
  • Position sensors at inlet and outlet points.
  • Record temperatures in a log for analysis.
  • Ensure measurements are taken under steady-state conditions.
  • Run chiller at full load and record performance metrics.
  • Switch to part-load conditions and repeat measurements.
  • Compare results to manufacturer specifications.
  • Document any discrepancies for further investigation.
  • Use energy meters to track consumption.
  • Calculate efficiency ratios based on input and output.
  • Log data for historical performance analysis.
  • Identify trends and areas for improvement.
  • Simulate fault conditions to activate alarms.
  • Verify alarm signals are audible and visible.
  • Check shutdown mechanisms for reliable operation.
  • Document results and any required adjustments.
  • Measure inlet and outlet temperatures at both units.
  • Calculate delta T by subtracting outlet from inlet.
  • Ensure readings are taken under normal operating conditions.
  • Record results for efficiency assessment.
  • Use flow meters to measure water flow rates.
  • Compare measured flow rates against design specs.
  • Adjust flow as necessary to meet specifications.
  • Document findings for compliance verification.
  • Inspect the expansion valve for proper function.
  • Measure superheat temperature at the evaporator outlet.
  • Adjust settings to maintain optimal performance.
  • Record adjustments and observations.
  • Use pressure gauges to measure system pressures.
  • Compare readings to the specifications provided by the manufacturer.
  • Identify any deviations and assess their impact.
  • Log all pressure data for reference.
  • Place thermometers at the discharge line of the compressor.
  • Record temperatures during normal operating conditions.
  • Ensure temperatures align with manufacturer guidelines.
  • Investigate any abnormal temperature readings.
  • Inspect cooling tower for proper water circulation.
  • Measure inlet and outlet temperatures of cooling water.
  • Log water flow rates to ensure compliance.
  • Document any maintenance needs identified.
  • Run the system at different load levels.
  • Record performance metrics for each load condition.
  • Evaluate stability and response time of the system.
  • Document findings for performance validation.
  • Introduce sudden load changes during testing.
  • Monitor how quickly the system adapts.
  • Record recovery times and any irregularities.
  • Analyze data for operational efficiency.
  • Listen for abnormal sounds while the system runs.
  • Use vibration analysis tools if available.
  • Identify and document any sources of concern.
  • Schedule follow-up inspections if issues are found.
  • Review control system settings against specifications.
  • Calibrate controls as necessary for optimal performance.
  • Document settings and calibration changes.
  • Ensure settings are saved and backed up.
  • Compile all recorded data into a comprehensive report.
  • Ensure clarity and accessibility of information.
  • Store documentation securely for future audits.
  • Review trends regularly for operational improvements.

8. Documentation and Reporting

9. Final Inspection and Clean-Up

  • Collect all tools used during maintenance.
  • Check all areas around the chiller for leftover materials.
  • Ensure no personal items are left behind.
  • Verify that all maintenance tasks are completed.
  • Remove lockout/tagout devices according to safety protocols.
  • Reconnect power supply and check for proper connections.
  • Start the chiller and monitor for unusual noises.
  • Check for proper operation of controls and indicators.
  • Ensure that the chiller reaches normal operating conditions.
  • Cross-check completed tasks against the checklist.
  • Ensure all signatures and dates are recorded.
  • Identify any outstanding tasks that need attention.
  • Collect all tools used during maintenance.
  • Check all areas around the chiller for leftover materials.
  • Ensure no personal items are left behind.
  • Verify that all maintenance tasks are completed.
  • Remove lockout/tagout devices according to safety protocols.
  • Reconnect power supply and check for proper connections.
  • Start the chiller and monitor for unusual noises.
  • Check for proper operation of controls and indicators.
  • Ensure that the chiller reaches normal operating conditions.
  • Cross-check completed tasks against the checklist.
  • Ensure all signatures and dates are recorded.
  • Identify any outstanding tasks that need attention.
  • Inspect each access panel for proper alignment.
  • Tighten screws or fasteners as necessary.
  • Ensure no panels are left open or loose.
  • Remove any tools, parts, or trash from the area.
  • Wipe down surfaces to remove spills or contaminants.
  • Ensure the worksite is tidy and safe for operation.
  • Look for water or refrigerant leaks around connections.
  • Check for physical damage to the chiller casing.
  • Report any abnormalities to the maintenance team.
  • Check that all safety guards are reinstalled correctly.
  • Verify that barriers are intact and positioned properly.
  • Ensure no safety devices are missing or damaged.
  • Check water levels in the system for adequacy.
  • Open vents to release any trapped air.
  • Ensure no leaks are present in the water system.
  • Record the date of maintenance completion.
  • Summarize findings and any corrective actions taken.
  • Ensure the log is accessible for future reference.
  • Summarize key observations from the maintenance.
  • Discuss potential improvements or repairs needed.
  • Document communication for future reference.
  • Inspect safety equipment for functionality.
  • Ensure equipment is stored in easily accessible locations.
  • Replace or repair any defective safety gear.
  • Determine the appropriate date for the next maintenance.
  • Record the date in the maintenance log.
  • Notify relevant personnel of the upcoming schedule.
  • Gather staff for a quick meeting post-maintenance.
  • Discuss any changes made to the chiller or procedures.
  • Answer any questions staff may have regarding updates.